Description
| Gen-set specifications | |
| Model | WPG500*76 |
| Standby Rating kVA/kWe | 625/500 |
| Prime Rating kVA/kWe | 560/450 |
| Voltage V | 220/127 |
| Frequency Hz | 60 |
| Power Factor | 0.8(lagging) |
| No. of Phases | 3 |
| Fuel consumption@25%/ 50% / 75%(L/h) | 35.3 / 61.8 / 90.7 |
| Fuel consumption@100% / 110%(L/h) | 122.8 / 138.2 |
| Sound@1m(dB·(A)) | Open≤105 ; Silence ≤95 |
| Ambient temp(℃) | -10~45 |
| Gen-set regulation class | ISO 8528-5 G2 |
| Steady-state voltage deviation | ≤±2.5% |
| Transient voltage deviation(100%sudden power decrease/increase) | ≤+25% ;≤-20% |
| Steady-state frequency band | ≤1.5% |
| Transient frequency deviation from rated frequency (100%sudden power decrease/increase) | ≤+12%;≤-10% |
| Standard Features | |||
| ♦ Electronic governor | ♦DC24V Electric starter | ♦ Deep-sea 7320MKII | |
| ♦ Closed water-cooled | ♦ IP23 | ♦H type insulation | |
| ♦ Air filter | ♦ Muffler | ♦ Circuit Breaker | |
| ♦Starting batteries | ♦ with connective wires | ♦ Radiator | |
| ♦Oil Drain Valve | ♦Forklift Groove | ♦Shock Absorber | |
| ♦ Color | Weichai blue (B,F) / beige canopy and black chassis (L) / white (C) | ||
| ♦ Packaging | packing case(B,F) / plastic wrap (L) / no packaging (C) | ||
| Options | |||
| ◇Line Voltage380V/415V | ◇Line Voltage 440V/480V | ◇Voltage 6.3kV/10.5kV /13.8kV | |
| ◇Single Voltage 220V/230V | ◇Automatic Transfer Switch | ◇Automatic Parallel system | |
| ◇Engine Heater (water) | ◇Engine Heater (air inlet) | ◇Alternator heater | |
| ◇External fuel tank(1000L/1500L) | ◇PMG/ AREP | ||